Permit: T11CM03707

Parcel: 110120960


Addresses:

5301 E GRANT RD


Inspection Status: Approved

Inspection History: PLUMBING - PROGRESS

Permit Number - T11CM03707

Inspection Description - PLUMBING - PROGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
03/19/2013 PLUMBING - PROGRESS Approved PER PLUMB FINAL
02/22/2013 PLUMBING - PROGRESS Partial Approval CLOSET GLANGES OK TO SET ALL TOILETS
02/21/2013 PLUMBING - PROGRESS Partial Approval IVRS - Inspection :* 1ST LEVEL CLOSET FLANGES, CORRECTIONS OK.
02/12/2013 PLUMBING - PROGRESS Partial Approval IVRS - Inspection :*
02/05/2013 PLUMBING - PROGRESS Partial Approval IVRS - Inspection :*CLOSET FLANGES 2ND LEVEL AND 4TH LEVEL WEST HALF
02/01/2013 PLUMBING - PROGRESS Partial Approval IVRS - Inspection :*
01/31/2013 PLUMBING - PROGRESS Partial Approval IVRS - Inspection :*LEVEL 4 ABV CEILING OK
LEVEL 4 NORTH AND WEST CORRIDOR CLOSET FLANGES OK
01/24/2013 PLUMBING - PROGRESS Partial Approval IVRS - Inspection :*
01/17/2013 PLUMBING - PROGRESS Denied IVRS - Inspection :
See detailed listing on site.| 999*
use proper tools to set closet flanges
12/18/2012 PLUMBING - PROGRESS Not ready for Inspection IVRS - Inspection :*
LEVEL 1 AREA C, CAFE INSTALLED PER UNAPPROVED P-401 AND P211 NOTE #3, WITH TEST OK, SUBJECT TO CITY REVIEWED AND APPROVED PLAN. NOTE; WASH AND RINSE COMPARTMENTS OF 3 COUP SINK REQUIRE A DIRECT CONNECTION. PROVIDE INSPECTOR WITH CITY APPROVED PLANS AS SOON AS YOU GET THEM. YOU HAVE SOME OUTSTANDING ITEMS WAITING ON PLAN REVIEW: SEE INSPECTION HISTORY (3 PERMITS)
L4 DOMESTIC WATER W/ 100PSI TEST OK WAITING ON REVISION FOR MATERIAL TYPE.
L4 SHOWER PAN LINERS W/ TEST OK. CALL FOR CLOSET FLANGE INSPECTIONS. NEED LABELS ABOVE CEILING COMPLETE PIPE INSULATION
12/07/2012 PLUMBING - PROGRESS Partial Approval 2ND LEVEL SHOWEROK
10/03/2012 PLUMBING - PROGRESS Partial Approval IVRS - Inspection :*
09/24/2012 PLUMBING - PROGRESS Not ready for Inspection PLASTIC PIPING SHALL BE TESTED WITH POTABLE WATE NOT AIR AS PRESCRIBED BY 2006 UPC 609.4
08/20/2012 PLUMBING - PROGRESS Not ready for Inspection PLUMBING NOTE#9 INSTALL CLEAN OUTS AT ALL SINKS.
07/26/2012 PLUMBING - PROGRESS Not ready for Inspection IVRS - Inspection :*
06/18/2012 PLUMBING - PROGRESS Not ready for Inspection IVRS - Inspection :*
POLYPROPYLENE DOMESTIC WATER REQUIRES APPROVAL FROM COT BUILDING OFFICIAL
NOTE ALL PIPING SHALL BE DEBURRED
NO PIPING MAY BE COVERED PRIOR TO TESTING
05/23/2012 PLUMBING - PROGRESS Partial Approval IVRS - Inspection :*
1) JOE HALL PLUMBING FOREMAN 631-1268 AND CHRIS W/ JE DUNN 400-3915