Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T11CM03707
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/12/2013 | PLUMBING - INTERMEDIATE | Approved | 3rd and 4th level flanges progress ok secure any loose closet bends pipe shall be even with top of flange revisions | |
01/28/2013 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
01/24/2013 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :*1ST AND 2ND LEVEL CLOSET FLANGES OK | |
01/04/2013 | PLUMBING - INTERMEDIATE | Partial Approval | 2ND & 3RD LEVEY SINKS INSTALLED PER PR 22, AND UNAPPROVED PLAN P221.2 &P231.2 PROVIDE CITY APPROVED REVISION | |
12/18/2012 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
12/13/2012 | PLUMBING - INTERMEDIATE | Partial Approval | FS AND WATER RELOCATE PER PR19 LEVEL 2 OK | |
11/28/2012 | PLUMBING - INTERMEDIATE | Partial Approval | 1. Second floor restroom relocate, subject to revised approved plan. | |
11/06/2012 | PLUMBING - INTERMEDIATE | Partial Approval | TR 30147-8- DOMESTIC WATER | |
11/01/2012 | PLUMBING - INTERMEDIATE | Partial Approval | DWV TESTS 42+43 4" LEVEL WITH TEST OK WATER PIPING IN WALLS W TEST OK LEVEL 1 TERMS 16009.-16011 AND CT ROOM 16199 DWV WATER AND CONDENSATE IN WALLS WITH TEST OK |
|
10/29/2012 | PLUMBING - INTERMEDIATE | Partial Approval | TEST #40 ) OK ONLY. | |
10/26/2012 | PLUMBING - INTERMEDIATE | Not ready for Inspection | TEST# 40 ) NOT HOLDING. | |
10/24/2012 | PLUMBING - INTERMEDIATE | Partial Approval | ||
10/23/2012 | PLUMBING - INTERMEDIATE | Partial Approval | WASTE AND VENT FOR TEST #38 AND #39. | |
10/18/2012 | PLUMBING - INTERMEDIATE | Partial Approval | STERILIZER PIPING FROM VALVE AT MAIN TO 1 FOOT DROP FROM CEILING TEST ONLY. AND MAKEUP WATER FROM DOWN STEAM SIDE OF BACKFLOW TO 1 FOOT DROP FROM CEILING. AND TEST FOR BOTTOM OF NO-HUB BANDS ON CLEAN OUTS FROM CORRIDOR 16101 NORTH AND CORRIDOR 16100 EAST ONLY 1ST FLOOR. | |
10/18/2012 | PLUMBING - INTERMEDIATE | Partial Approval | STERILIZER ROOM 20527 CA PIPING FROM VALVE AT MAINS STUB DOWN THUR CEILING 1' TESTED ONLY. | |
10/11/2012 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
10/10/2012 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
10/09/2012 | PLUMBING - INTERMEDIATE | Cancelled | IVRS - RI canceled | |
10/08/2012 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
10/04/2012 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
10/03/2012 | PLUMBING - INTERMEDIATE | Partial Approval | TEST 34-35, 4TH LEVEL OK WATER TESTING 4TH LEVEL | |
09/28/2012 | PLUMBING - INTERMEDIATE | Partial Approval | DOMESTIC WATER IN WALLS AND HARD LIDS LEVEL 4 COLS A-F. DWV TEST 33. CLEAN OUT CORRECTIONS OK | |
09/26/2012 | PLUMBING - INTERMEDIATE | Partial Approval | DWV TEST #30 AND #31 OK SUPPORT TRRAP ARMS OR TRAPS INSTALL 4" CO AS REQUIRED TEST #32 IN WALLS OK, PROVIDE 4" CO AT UPPER TERMINAL DOMESTIC WATER IN WALLS AND ABV HARD LIDS 4TH LEVEL FROM COLD A-F OK | |
09/24/2012 | PLUMBING - INTERMEDIATE | Partial Approval | DWV TESTS 28.29 DWV AND WATER DISCONTAMINATION RM WEST WALL OK TO COVER | |
09/21/2012 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
09/20/2012 | PLUMBING - INTERMEDIATE | Partial Approval | DWV TESTS 25,26,27 LEVELS 2 AND 3 AREA B- OK DOMESTIC WATER IN WALLS; STERILIZER CORR 30274, 3RD LEVEL PR'S, PHARMACY, SCRUB 30276 PACU 20, CLEAN 30167 IN WALLS AND OVERHEAD 30254, NURSES 30244 |
|
09/18/2012 | PLUMBING - INTERMEDIATE | Partial Approval | TESTS 20,21,23 AND 24 WITH CORRECTIONS OK | |
09/14/2012 | PLUMBING - INTERMEDIATE | Denied | DWV TEST IN 20 IN WALLS OK COMPLETE WORK ABV CEILING LEVEL 1, DWV TEST 21 CORRECT PIPE AND CORRECT SIZE AT UPPER END. TEST DOWN AT BLOWN FITTINGS | |
09/11/2012 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
09/07/2012 | PLUMBING - INTERMEDIATE | Partial Approval | DWV TEST #17 AREA LEVELS 3 AND 4 OK | |
09/05/2012 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
08/31/2012 | PLUMBING - INTERMEDIATE | Partial Approval | STAFF 30538-37 DMV BELOW FLOOR OK, COMPLETE WORK IN WALLS, 1ST LEVEL DWV WATER TEST FROM RM 16130 NORTH TO FCO AT COLD 3/K. AREA A DOMESTIC WATER IN WALLS, L3 TEST OK | |
08/29/2012 | PLUMBING - INTERMEDIATE | Partial Approval | 3RD LEVEL WATER IN WALLS ONLY. C015 A-H DWV RM 30238= COMPLETE WORK, CORRECT VENT SIZE. |
|
08/28/2012 | PLUMBING - INTERMEDIATE | Partial Approval | DWV+WATER IN WALLS +COLS CORR 20450 OK TO COVER | |
08/27/2012 | PLUMBING - INTERMEDIATE | Partial Approval | DWB TESTS #13 AND #14 WND TO 3RD LEVEL. SINKS CORR 20450 L 2 + 3. DOM WATER IN WALLS PAUS L3 SOUTH WALL. |
|
08/23/2012 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
08/20/2012 | PLUMBING - INTERMEDIATE | Partial Approval | 2ND LEVEL COPPER IN WALLS | |
08/17/2012 | PLUMBING - INTERMEDIATE | Partial Approval | 1. Test #12 OK. 2. Prep storage #20542, #20503, #20505, #20506, Janitors closet #20335, N/H DWV in walls OK to cover after insulation. | |
08/16/2012 | PLUMBING - INTERMEDIATE | Partial Approval | 1. second floor lavatory revent OK. 2. Roof drain and overflow drain for third floor OK. 3. Rooms #20534, rooms #20533, 20538, storage #20541 walls, 4. Test #10 and test #11 OK 5. OK to cover bathroom walls as readied. | |
08/13/2012 | PLUMBING - INTERMEDIATE | Partial Approval | WATER PIPING TRS 20465 AND 20466 OK RETEST DWV FOR CHANGES TO LAV REVENT |
|
08/08/2012 | PLUMBING - INTERMEDIATE | Partial Approval | DOMESTIC WATER IN WALLS WITH LOOPS, AIR TEST, WEST OF CORRIDOR 20368, AND SOUTH OF 20450 | |
08/07/2012 | PLUMBING - INTERMEDIATE | Partial Approval | DOMESTIC WATER WITH TEST OK. 20423, 20408 TRS AND SINKS. | |
08/06/2012 | PLUMBING - INTERMEDIATE | Partial Approval | TEST 6-8 DWV OK, NEED RWL AND 3RD LEVEL WASTE TEST IN CHASES PRIOR TO COVERING. TEST 9 DWV AND WATER IN WALLS OK | |
08/02/2012 | PLUMBING - INTERMEDIATE | Partial Approval | ROOM 20522 HOSPITALITY DWV AND WATER IN WALLS ALL TEST OK | |
08/01/2012 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
07/31/2012 | PLUMBING - INTERMEDIATE | Partial Approval | OK TO INSULATE HW DROPS IN WALLS. L COPPER WITH LOOPS, TEST LEVEL 2: PR 6-17, AND NURSES R6-R8. PLEASE TRY TO COORDINATE DWV AND DOMESTIC WATER TESTING AT EACH LOCATION. DECONTAMINATION FLOOR SINKS OK. SOUTH WALL HYDRANTS OK. | |
07/26/2012 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
07/25/2012 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
07/24/2012 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
07/18/2012 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
06/18/2012 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
05/30/2012 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) REMOVE TEST BLOCKS, REINSTALL PIPING AND OFF SETS AND CLEANOUTS TEST SO THAT NO JOINT OR PIPE IN THE BLDG IS TESTED WITH LESS THAN A 10 FOOT READ 2) CLEANOUTS REQUIRED FOR STORM DRAIN UNDER SLAB |