Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T11CM03707
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/14/2013 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
03/08/2013 | ELECTRIC - INTERMEDIATE | Partial Approval | 1. LEVEL 2 # 6-12 + #1-6 PACO ROOMS OK 2. NURSE CALLS AREA B 3RD FLOOR LOW VOLTAGE OK 3. COUNTERS 30-143 ROM 30150 ABOVE CEILING OK 4. FIRST FLOOR RECEPTION COUNTER MILL WORK OK 16004 |
|
03/06/2013 | ELECTRIC - INTERMEDIATE | Partial Approval | 1. HIGH VOLTAGE OK SECOND FLOOR 2. LOW VOLTAGE NOT READY 3. 20465,20456,20311, HOSPIT 20314 STAIRWAY C 4. THIRD FLOOR 30285,30301A,30143 IJ 30289,30291. HIGH VOLTAGE OK LOW VOLTAGE NOT READY |
|
02/26/2013 | ELECTRIC - INTERMEDIATE | Partial Approval | 1. area a level 3 southeast hallway and prooms and paco care units above ceiling ok 2. hallway 30210 electric above ceiling only ok low voltage not ready |
|
02/20/2013 | ELECTRIC - INTERMEDIATE | Partial Approval | 1. CANOPY LIFTING AREA D OK 2. 16118 HALLWAY |
|
02/12/2013 | ELECTRIC - INTERMEDIATE | Cancelled | IVRS - RI canceled | |
02/01/2013 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) LEVEL AND HARD LID ELEVATOR CAN LITES 2) 4TH FLOOR NURSES STATION 40004 OK |
|
01/31/2013 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
01/29/2013 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
01/25/2013 | ELECTRIC - INTERMEDIATE | Partial Approval | FIRE PUMP DISCONNECTS OK | |
01/24/2013 | ELECTRIC - INTERMEDIATE | Partial Approval | 1 PRI PEDS 20343, 20342,20341, 20351, 20357 PR6 THRU 21 LOW VOLTAGE STILL HAS TO BE INSPECTED 20423 CAN LITES OK | |
01/23/2013 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
01/17/2013 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
01/15/2013 | ELECTRIC - INTERMEDIATE | Partial Approval | 1. 2ND FLOOR AREA A CEILINGS, PATIENT ROOMS LEFT TO INSPECT 1 THRU 24. 2. LOUNGE 30294 3. LOUNGE 30293 4.30292 LOCKER 30290 ROOMS 5.30287 CORRIDOR 30275 CORRIDOR 6.30225, 30223, 30278, 30216, 30217, 30218, 30215, 30214, 30277, 30276, 30290, 30292, 30293, 30287, 30294, 30295 CEILINGS OK |
|
01/10/2013 | ELECTRIC - INTERMEDIATE | Partial Approval | 1. VFD SEF 2 SUK 9 & SEF3 SUK9 2. CHW P-3 CHW P-4 3. CORRIDOR 40003,40006, 40043, 40044 4. PR ROOMS 41001 THRU 41040 HIGH VOLTAGE ONLY 5. ABOVE CEILING CORE 40004 THRU 40042 6. NURSES STATIONS 20404,20414 |
|
01/08/2013 | ELECTRIC - INTERMEDIATE | Partial Approval | 1. se8 /lem main electrical room ok 2. front landscape lighting ok 3. elevator lobby 30141 corridor 30210 elevator room |
|
01/04/2013 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
01/02/2013 | ELECTRIC - INTERMEDIATE | Partial Approval | ok ltg /power with exception to lv cabling at pack u and pr areas need ci fictures speaker and fa's to have sismer to structure this is for 2nd and 3rd floors | |
12/26/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK ABOVE CEILING LOBBY # 16603 OK WALLS ROOMS, 20446, 20488. |
|
12/21/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | 1. 2ND FLOOR OR #1 ROOM CEILING OK, OR #5 CEILING OK OR #7 CEILING OK 2. 4TH FLOOR CEILING 277V LITING AND POWER ONLY 41021 THRU 41030, 40025 THRU 40027, 40030, 40031, 40034, 40035, 40038, 40039, 40039A, 40040 THRU 40042 3. CEILINGS 16332,16334 THRU 337, 16328,16313-319, 16290-294, HALLWAY 16106-107, 16308-311, 16302-305, 16295-300, 16320-323, 16174-191, 16193,16160-164 HALLWAYS 16144, 16145, 16164, 16166-173 4. DR 81-T01-LCBB T01.LA, 701 PCBB, T01-PA TO1-PB, T01PC, T01PD T01LBCBC |
|
12/18/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1.3RD FLOOR COMM ROOM 30222 OK 2. 4TH FLOOR ALL ST FAN UNITS & STFCUS OK 3 2ND FLOOR COM ROOM 20392 OK |
|
12/17/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | 1.S3PCBB 2.S3PCBN 3.S3PCBD 4.S3PCBF 5. S3PCBJ 6. S3PCBH 7. S3ICBO PANELS OK |
|
12/13/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. 16111-16117 WALLS ROUGH 2. ST UNITS LEVEL 1,2,3 3. 16100 LOW HARD LIDS CAN LITES OK |
|
12/12/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | S3-T. PEBB-A, AHU 313, EF25PD, EF PEDWAIT, S1LLSA, S1PLSA T-T01-PCBA, T-T01-PA, S1-T01-PCBC, DR81-T01-LCBA, DR81-T01-LA, DR81-T01=8A S1-T01-8A S1-TO1-PCBA, S4PE, S4-PD, PC, PB, PA, S4 PCBA, S4 PCBB, S4 PCBC, S4 PCBO S4-LA, S4, LCBA OK REDUNDENT GROUNDING TO PATIENT CARE ROOMS ON PANELS OK LEVEL 2,3,4,AND 10 SOLID OK |
|
12/11/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
12/06/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | s4-llsa, s4-plsa, s4 plsa panels ok 4th floor s3pd panel 3rd floor, DR83-pa panel 3rd floor 1st floor radiology breakers 6 all ok t-s1-pb transformer 1st floor 20314, 20315, 20311, 20312,20313 power data rooms ok 1,5,7 rooms ok 2nd floor |
|
12/05/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
12/04/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | 1. 30142 30150 AN RECEPTION AREA AND CONFERENCE AREA OK 2. PANELS ELETRICAL ROOM 30213 S3 AND LLSA.S3 P1SA AND S3P1SB S3.OA_S3PB+S3PC+S3PE +SCPF+S3LCBA+S3..LA S3.PCBO S3.PCBP S3PCBO |
|
11/30/2012 | ELECTRIC - INTERMEDIATE | Denied | 1. FIXTURE WHIPS TO MEET REQUIREMENTS OF 517.13 (A)(B) FOR CRITICAL AND LIFE SAFETY BRANCHES AND PATIENT CARE AREAS 2. CONNECT FLEX CONNECTOS TO FLEX 3. FINISH VDV CAVBELING AND CONTROL CIRCUITS 725.8 760.24 770.24 800.24 |
|
11/28/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | OK SB-PEBA, S2-LEBA DR82-PCBA, DR83-PCBA CHECK PANEL COVER AND LABELING ON FINAL 110.12,110.19, 408.4 1) PANEL S2-LEBA HAS NO NEUTRAL/GROUNDED CONNECTION AND HAS 277V BREAKER INSTALLED. |
|
11/26/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | ) LABEL ROOF DISCONNECTS BEFORE FINAL 2) PANEL S3-LEBA HAS 277 V BREAKERS AND NO CONNECTED NEUTRAL/ GROUNDED CONDUCTOR ALSO S2-LEBA OK ROOF UNITS EXCEPT AS NOTED OK VFD'S EF 1,2,3,4150,2150,3150,2180PR,3150PR, PMED GAS OK T84-PLST, DR84 PA DR84-PCBA OK 4TH FLOOR GROUND BAR 400207 OK 21D 40020 30213 OK 3RD FLOOR GROUND BAR OK TS3-PLSA, S3-LEBA OK T52-PLSA, S2-LLSA, S2-PLSA, S2 PLSB, S2-PA, S2-PB, S2-PC, S2-PF, S2-LCPA, 52LA S2-PCBO, S2-PCBB, S2-PLBQ, S2 -PLQR, S2-PCBS, S2-PLBT OK 2ND FLOOR GROUND BAR 20468 |
|
11/21/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
11/20/2012 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | PARTIAL OK TO TS3-PCBA DR 83-PCBA | |
11/19/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
11/16/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | OK TDR84-PA,TDC 84-PC BA DISCO DR 84-PA,SP#LEBA SPH PEBA,TSP PA OK CONTROLS |
|
11/15/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | 1. maintain illumination at electrical equipment 2. maintain dedicated space above electrical equipment |
|
11/14/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | DO NOT ENERGIZE AIR HANGERS UNITL ALL INSPECTIONS COMPLETE. OK PUMP HEADS, OK VFD CWP 1/2 HWP 1&2, OK GUTTERS AND PIPE BY AHU-2B, OK CHILLER #1, OK AHU- 4A & 4B, AHU 2A&2B, AHU 8, AHU 6, AHU3, AHU7, AHU5, AHU1. OK DR81-LA, DR81-LCBB, PRSI-LCBA, OK TSI-PLSA,TSI-PA, TDR82-PCBA,TDR82-PA, TDR83-PCBA, IDR23-PA. 1. ROOF TOP RECEPTACLE COVERS TO BE PER 406.8 2. FINISH WIRING CONTROLSFOR AHU UNITS 3. FILL UNUSEDBOX OPENINGS-CONTROL WIRING 4. FINISH LIGHTS AHU UNITS 5. LOOSE FITTING CONTROLS |
|
11/09/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
11/08/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | OK ATS-1,2,3,4,5,6,7 OK S8L-1,2 88LE-1,3,4,5, OK DR 81- EBA, PEBA (MAIN ONLY) T-S1-PBEA, T-PH-PEBA OK WALLS AND LIDS 20478, 4048 20482 PER PR #19 |
|
11/06/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
11/05/2012 | ELECTRIC - INTERMEDIATE | Cancelled | IVRS - RI canceled | |
11/01/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | OK HARD LIDS 4100A-41005A 41031A 41040A 30171 OK CORRIDOOR 40044 LID OK COORIDOOR WALLS 30210 |
|
10/29/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | 4TH FLOOR HARDLID 40004; 3RD FLOOR STORAGE 30314, TOILETS 30147, 30148, CORRIDOR 146, WALLS GRIDLINE H & GRIDLINE 3 RECEP 30142 |
|
10/25/2012 | ELECTRIC - INTERMEDIATE | Cancelled | IVRS - RI canceled | |
10/23/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | 4TH FLOOR HARD LIDS 20348, OR 3, OR 9, OR 11, OR 15, OR 2, OR 4, OR 6, OR 8, OR 10, OR 12 & OR 14 2ND FLOOR 40022 THROUGH 40024,40026, 40006, 40044, CORADOR HARD LIDS 1ST FLOOR HARD LIDS & WALLS 16198, 16199, 16284, 16282, 16285, 16287 |
|
10/19/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | OK WALLS 40004-40005A, 40018,40018A,40019 | |
10/18/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
10/15/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | OK 2 ROOM 20442 30264-30267,30212,30158,41018A,41020A,41002 OK SHAFT WALLS 40031 |
|
10/12/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | 4TH FLOOR 8 1.FINISH ROOM 41002 (CLIMATIC) 2. PLEASE VERIFY AHJ INSPECTION AT SHAFT WALLS OK WALL ROOMS 40008-40016,40027,4003D,40031,40035, 40040, 41001-41005. OK LIDS ROOMS 40028, 40029, 40033,41005A-41010A 3RD FLOOR 8 OK WALLS 30268-30271, 30274 OK LID 30203A 4TH FLOOR 8 OK WALLS 20440,20434,20432,20430,20355 |
|
10/08/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | DR8-EBB EM PANEL 1/- FOR TEMP ONLY OK USED LOCK OUT TAG OUT | |
10/04/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | OK CANS BATHROOM LIDS 41011A-4107A,4019A,41021A-41030A | |
10/02/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | OK WALLS 20362, PARTIAL 20359(NORTH, SOUTH, WEST) OR 6,8,15 | |
09/28/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | OK CANS SOFFITTS 30291, 30289, 30163, 30173, 30302-30306 OR 3,9,11 2ND FLOOR | |
09/27/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | OK WALLS ROOMS 20504,20504A | |
09/26/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | CORRIDORS: 30288,30224,30230,30211,30178,30155 HARD LIDS:30219,30165,30166,30168,30169,30249,30250,30238,30239,30253A SOFFITS:30243,30234 ROOMS: 30170,30175,30174,30171,30173 |
|
09/21/2012 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | CANCELLED | |
09/20/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | OK WALLS 4100.5 41018 40039A 400-40044 | |
09/14/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | OK WALLS -30177 30179 30180 30195 30207 30156 30162 30151 30152 FOR PR LOCATIONS | |
09/12/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | 1. ELEVATOR ELETRIC ROOM MAINTAIN WORKING SPACE CLEARANCES 110.26 (A)(1) TABLE CONDITION 3 | |
09/06/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | CRITICAL POWER HARD PIPED ROOM # 3232,3253,3253A, 3252, NORMAL POWER MC PACUWALLS 3246,3242,3233,3251,3245,3241 | |
09/05/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | ROOMS 30248, 30220, 30225, 30273, 30272, 30293, 30275, 30277 | |
09/04/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | NO INSPECTION ROOM 20408, 20312, 20368, 20363 WEST WALL | |
08/31/2012 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
08/30/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | ROOMS 20423A,20419,20420,20409,20383A,20365,20347,20348,20349,20361,20392,20389,20485,20484,20483,20447,20481,20482,20350,20358,20359,20345 | |
08/29/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | ROOMS PR.11. 1 THRU 8 CORRIDORS 20492 AND 20360 COLUMNS #1B,1D,1C,1F,1H |
|
08/27/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | 1. p.r. 9-10, 12-21 2. rms. 20364, 20347,20345, 20367, 20366, 20365, 20423a 3. soffits 20312, 20355,2;circles,20346,20367. |
|
08/24/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | 1. REINSPECT MC CABLE CFR CIRCUITS IN CONDUIT 2. PACU 7-15, 16-20, 21-24, 1-6 3. PEDS 1-6 4. EQUIPMENT ROOM 20447 5. 20450 CORIDOR 20463 |
|
08/23/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | OK WALLS ROOMS 20527, 20542, 20505, COLUMNS 20528A, 30163-30169, 30222,30313,30316,30317 * PACU UNITS BEING REPIPED PER 517.30(C)(3) |
|
08/17/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | MEET WITH ENGINEER TO DISCUSS ELECTRICAL ROOMS. IT WAS DETERMINED TO ADD DOORS OK WALLS PR 6-20 |
|
08/16/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | FINISH VDV ROOM 20382 OK WALLS ROOMS PACU 1-6 (PEDS) PR1-5 20356, 20383A, PR21 |
|
08/14/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | OK SOUTH AND WEST EXTERIOR WALLS RM 50000 | |
08/13/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
08/10/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | OK WALL 20385, 20407-20410, 204017-204120, 20405, 20413 PACU UNITS #10-20, #1-6 |
|
08/02/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | OK RECESSED CANS SOFFITTS 20404,20414, 16004B OK WALLS 16003 NORTH AND WEST VDV CABLING TO BE AS PER 725.3 AND 8, 760.3 AND 24, 800.3 AND 24 |
|
08/01/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | PLEASE VERIFY EGRESS LIGHTING FOR ROOMS 20468, 20469, 30293, 30294 PLEASE VERIFY ADEQUATE LIGHTING FRO EGRESS ROOM 30316, 30317, OK WALLS ROOMS 30234, 30237-40, 30243, 30247-50, 30300-30305, 30301A, 30306, 30312, 30315, 30285, 30287, 20366, 16324-16328 |
|
07/26/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* NOTE STRAIGHT PULL IN BOXES 3/4 28 ALSO DETAIL 276.32 66.32 OK WALLS ROOMS 30214-30219 30223 30289 30292 30294 30295 |
|
07/23/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* RM 50,000 WEST EQUIPMENT PLATFORM LIGHTING NORTH SOUTH AND WEST WALLS PENHOUSE OK |
|
07/19/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK COLUMN 1G, 1H, 1C, 2A OK WALLS ROOMS 11169 (SOUTH), 16003 (EAST, 16005 (NORTH) |
|
07/18/2012 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
07/16/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
07/10/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
07/06/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
07/03/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
06/27/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
05/10/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) NORTH OUTSIDE WALL 5 LIGHTS OK |