Permit: T11CM03707

Parcel: 110120960


Addresses:

5301 E GRANT RD


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T11CM03707

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
03/14/2013 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
03/08/2013 ELECTRIC - INTERMEDIATE Partial Approval 1. LEVEL 2 # 6-12 + #1-6 PACO ROOMS OK
2. NURSE CALLS AREA B 3RD FLOOR LOW VOLTAGE OK
3. COUNTERS 30-143 ROM 30150 ABOVE CEILING OK
4. FIRST FLOOR RECEPTION COUNTER MILL WORK OK 16004
03/06/2013 ELECTRIC - INTERMEDIATE Partial Approval 1. HIGH VOLTAGE OK SECOND FLOOR
2. LOW VOLTAGE NOT READY
3. 20465,20456,20311, HOSPIT 20314 STAIRWAY C
4. THIRD FLOOR 30285,30301A,30143 IJ 30289,30291. HIGH VOLTAGE OK LOW VOLTAGE NOT READY
02/26/2013 ELECTRIC - INTERMEDIATE Partial Approval 1. area a level 3 southeast hallway and prooms and paco care units above ceiling ok

2. hallway 30210 electric above ceiling only ok low voltage not ready
02/20/2013 ELECTRIC - INTERMEDIATE Partial Approval 1. CANOPY LIFTING AREA D OK
2. 16118 HALLWAY
02/12/2013 ELECTRIC - INTERMEDIATE Cancelled IVRS - RI canceled
02/01/2013 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :* 1) LEVEL AND HARD LID ELEVATOR CAN LITES
2) 4TH FLOOR NURSES STATION 40004 OK
01/31/2013 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
01/29/2013 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
01/25/2013 ELECTRIC - INTERMEDIATE Partial Approval FIRE PUMP DISCONNECTS OK
01/24/2013 ELECTRIC - INTERMEDIATE Partial Approval 1 PRI PEDS 20343, 20342,20341, 20351, 20357 PR6 THRU 21 LOW VOLTAGE STILL HAS TO BE INSPECTED 20423 CAN LITES OK
01/23/2013 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
01/17/2013 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
01/15/2013 ELECTRIC - INTERMEDIATE Partial Approval 1. 2ND FLOOR AREA A CEILINGS, PATIENT ROOMS LEFT TO INSPECT 1 THRU 24.
2. LOUNGE 30294
3. LOUNGE 30293
4.30292 LOCKER 30290 ROOMS
5.30287 CORRIDOR 30275 CORRIDOR
6.30225, 30223, 30278, 30216, 30217, 30218, 30215, 30214, 30277, 30276, 30290, 30292, 30293, 30287, 30294, 30295 CEILINGS OK
01/10/2013 ELECTRIC - INTERMEDIATE Partial Approval 1. VFD SEF 2 SUK 9 & SEF3 SUK9
2. CHW P-3 CHW P-4
3. CORRIDOR 40003,40006, 40043, 40044
4. PR ROOMS 41001 THRU 41040 HIGH VOLTAGE ONLY
5. ABOVE CEILING CORE 40004 THRU 40042
6. NURSES STATIONS 20404,20414
01/08/2013 ELECTRIC - INTERMEDIATE Partial Approval 1. se8 /lem main electrical room ok
2. front landscape lighting ok
3. elevator lobby 30141 corridor 30210 elevator room
01/04/2013 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
01/02/2013 ELECTRIC - INTERMEDIATE Partial Approval ok ltg /power with exception to lv cabling at pack u and pr areas need ci fictures speaker and fa's to have sismer to structure this is for 2nd and 3rd floors
12/26/2012 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :* OK ABOVE CEILING LOBBY # 16603
OK WALLS ROOMS, 20446, 20488.
12/21/2012 ELECTRIC - INTERMEDIATE Partial Approval 1. 2ND FLOOR OR #1 ROOM CEILING OK, OR #5 CEILING OK OR #7 CEILING OK
2. 4TH FLOOR CEILING 277V LITING AND POWER ONLY 41021 THRU 41030, 40025 THRU 40027, 40030, 40031, 40034, 40035, 40038, 40039, 40039A, 40040 THRU 40042
3. CEILINGS 16332,16334 THRU 337, 16328,16313-319, 16290-294, HALLWAY 16106-107, 16308-311, 16302-305, 16295-300, 16320-323, 16174-191, 16193,16160-164 HALLWAYS 16144, 16145, 16164, 16166-173
4. DR 81-T01-LCBB T01.LA, 701 PCBB, T01-PA TO1-PB, T01PC, T01PD T01LBCBC
12/18/2012 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1.3RD FLOOR COMM ROOM 30222 OK
2. 4TH FLOOR ALL ST FAN UNITS & STFCUS OK
3 2ND FLOOR COM ROOM 20392 OK
12/17/2012 ELECTRIC - INTERMEDIATE Partial Approval 1.S3PCBB 2.S3PCBN 3.S3PCBD 4.S3PCBF 5. S3PCBJ 6. S3PCBH
7. S3ICBO PANELS OK
12/13/2012 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. 16111-16117 WALLS ROUGH
2. ST UNITS LEVEL 1,2,3
3. 16100 LOW HARD LIDS CAN LITES OK
12/12/2012 ELECTRIC - INTERMEDIATE Partial Approval S3-T. PEBB-A, AHU 313, EF25PD, EF PEDWAIT, S1LLSA, S1PLSA
T-T01-PCBA, T-T01-PA, S1-T01-PCBC, DR81-T01-LCBA, DR81-T01-LA, DR81-T01=8A
S1-T01-8A S1-TO1-PCBA, S4PE, S4-PD, PC, PB, PA, S4 PCBA, S4 PCBB, S4 PCBC, S4 PCBO
S4-LA, S4, LCBA OK
REDUNDENT GROUNDING TO PATIENT CARE ROOMS ON PANELS OK LEVEL 2,3,4,AND 10 SOLID OK
12/11/2012 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
12/06/2012 ELECTRIC - INTERMEDIATE Partial Approval s4-llsa, s4-plsa, s4 plsa panels ok 4th floor
s3pd panel 3rd floor, DR83-pa panel 3rd floor
1st floor radiology breakers 6 all ok
t-s1-pb transformer 1st floor
20314, 20315, 20311, 20312,20313 power data rooms ok
1,5,7 rooms ok 2nd floor
12/05/2012 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
12/04/2012 ELECTRIC - INTERMEDIATE Partial Approval 1. 30142 30150 AN RECEPTION AREA AND CONFERENCE AREA OK
2. PANELS ELETRICAL ROOM 30213 S3 AND LLSA.S3 P1SA AND S3P1SB S3.OA_S3PB+S3PC+S3PE +SCPF+S3LCBA+S3..LA S3.PCBO S3.PCBP S3PCBO
11/30/2012 ELECTRIC - INTERMEDIATE Denied 1. FIXTURE WHIPS TO MEET REQUIREMENTS OF 517.13 (A)(B) FOR CRITICAL AND LIFE SAFETY BRANCHES AND PATIENT CARE AREAS
2. CONNECT FLEX CONNECTOS TO FLEX
3. FINISH VDV CAVBELING AND CONTROL CIRCUITS 725.8 760.24 770.24 800.24
11/28/2012 ELECTRIC - INTERMEDIATE Partial Approval OK SB-PEBA, S2-LEBA DR82-PCBA, DR83-PCBA
CHECK PANEL COVER AND LABELING ON FINAL 110.12,110.19, 408.4
1) PANEL S2-LEBA HAS NO NEUTRAL/GROUNDED CONNECTION AND HAS 277V BREAKER INSTALLED.
11/26/2012 ELECTRIC - INTERMEDIATE Partial Approval ) LABEL ROOF DISCONNECTS BEFORE FINAL
2) PANEL S3-LEBA HAS 277 V BREAKERS AND NO CONNECTED NEUTRAL/ GROUNDED CONDUCTOR ALSO S2-LEBA
OK ROOF UNITS EXCEPT AS NOTED
OK VFD'S EF 1,2,3,4150,2150,3150,2180PR,3150PR, PMED GAS
OK T84-PLST, DR84 PA DR84-PCBA OK 4TH FLOOR GROUND BAR 400207 OK 21D 40020 30213 OK 3RD FLOOR GROUND BAR OK TS3-PLSA, S3-LEBA
OK T52-PLSA, S2-LLSA, S2-PLSA, S2 PLSB, S2-PA, S2-PB, S2-PC, S2-PF, S2-LCPA, 52LA S2-PCBO, S2-PCBB, S2-PLBQ, S2 -PLQR, S2-PCBS, S2-PLBT OK 2ND FLOOR GROUND BAR 20468
11/21/2012 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
11/20/2012 ELECTRIC - INTERMEDIATE Not ready for Inspection PARTIAL OK TO TS3-PCBA DR 83-PCBA
11/19/2012 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
11/16/2012 ELECTRIC - INTERMEDIATE Partial Approval OK TDR84-PA,TDC 84-PC BA DISCO DR 84-PA,SP#LEBA SPH PEBA,TSP PA
OK CONTROLS
11/15/2012 ELECTRIC - INTERMEDIATE Partial Approval 1. maintain illumination at electrical equipment
2. maintain dedicated space above electrical equipment
11/14/2012 ELECTRIC - INTERMEDIATE Partial Approval DO NOT ENERGIZE AIR HANGERS UNITL ALL INSPECTIONS COMPLETE.
OK PUMP HEADS, OK VFD CWP 1/2 HWP 1&2, OK GUTTERS AND PIPE BY AHU-2B, OK CHILLER #1, OK AHU- 4A & 4B, AHU 2A&2B, AHU 8, AHU 6, AHU3, AHU7, AHU5, AHU1.
OK DR81-LA, DR81-LCBB, PRSI-LCBA, OK TSI-PLSA,TSI-PA, TDR82-PCBA,TDR82-PA, TDR83-PCBA, IDR23-PA.
1. ROOF TOP RECEPTACLE COVERS TO BE PER 406.8
2. FINISH WIRING CONTROLSFOR AHU UNITS
3. FILL UNUSEDBOX OPENINGS-CONTROL WIRING
4. FINISH LIGHTS AHU UNITS
5. LOOSE FITTING CONTROLS
11/09/2012 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
11/08/2012 ELECTRIC - INTERMEDIATE Partial Approval OK ATS-1,2,3,4,5,6,7
OK S8L-1,2 88LE-1,3,4,5,
OK DR 81- EBA, PEBA (MAIN ONLY)
T-S1-PBEA, T-PH-PEBA
OK WALLS AND LIDS 20478, 4048 20482 PER PR #19
11/06/2012 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
11/05/2012 ELECTRIC - INTERMEDIATE Cancelled IVRS - RI canceled
11/01/2012 ELECTRIC - INTERMEDIATE Partial Approval OK HARD LIDS 4100A-41005A 41031A 41040A 30171
OK CORRIDOOR 40044 LID OK COORIDOOR WALLS 30210
10/29/2012 ELECTRIC - INTERMEDIATE Partial Approval 4TH FLOOR HARDLID 40004;
3RD FLOOR STORAGE 30314, TOILETS 30147, 30148, CORRIDOR 146, WALLS GRIDLINE H & GRIDLINE 3 RECEP 30142
10/25/2012 ELECTRIC - INTERMEDIATE Cancelled IVRS - RI canceled
10/23/2012 ELECTRIC - INTERMEDIATE Partial Approval 4TH FLOOR HARD LIDS 20348, OR 3, OR 9, OR 11, OR 15, OR 2, OR 4, OR 6, OR 8, OR 10, OR 12 & OR 14
2ND FLOOR 40022 THROUGH 40024,40026, 40006, 40044, CORADOR HARD LIDS
1ST FLOOR HARD LIDS & WALLS 16198, 16199, 16284, 16282, 16285, 16287
10/19/2012 ELECTRIC - INTERMEDIATE Partial Approval OK WALLS 40004-40005A, 40018,40018A,40019
10/18/2012 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
10/15/2012 ELECTRIC - INTERMEDIATE Partial Approval OK 2 ROOM 20442
30264-30267,30212,30158,41018A,41020A,41002 OK SHAFT WALLS 40031
10/12/2012 ELECTRIC - INTERMEDIATE Partial Approval 4TH FLOOR 8
1.FINISH ROOM 41002 (CLIMATIC)
2. PLEASE VERIFY AHJ INSPECTION AT SHAFT WALLS
OK WALL ROOMS 40008-40016,40027,4003D,40031,40035, 40040, 41001-41005.
OK LIDS ROOMS 40028, 40029, 40033,41005A-41010A

3RD FLOOR 8
OK WALLS 30268-30271, 30274
OK LID 30203A

4TH FLOOR 8
OK WALLS 20440,20434,20432,20430,20355
10/08/2012 ELECTRIC - INTERMEDIATE Partial Approval DR8-EBB EM PANEL 1/- FOR TEMP ONLY OK USED LOCK OUT TAG OUT
10/04/2012 ELECTRIC - INTERMEDIATE Partial Approval OK CANS BATHROOM LIDS 41011A-4107A,4019A,41021A-41030A
10/02/2012 ELECTRIC - INTERMEDIATE Partial Approval OK WALLS 20362, PARTIAL 20359(NORTH, SOUTH, WEST) OR 6,8,15
09/28/2012 ELECTRIC - INTERMEDIATE Partial Approval OK CANS SOFFITTS 30291, 30289, 30163, 30173, 30302-30306 OR 3,9,11 2ND FLOOR
09/27/2012 ELECTRIC - INTERMEDIATE Partial Approval OK WALLS ROOMS 20504,20504A
09/26/2012 ELECTRIC - INTERMEDIATE Partial Approval CORRIDORS: 30288,30224,30230,30211,30178,30155
HARD LIDS:30219,30165,30166,30168,30169,30249,30250,30238,30239,30253A
SOFFITS:30243,30234
ROOMS: 30170,30175,30174,30171,30173
09/21/2012 ELECTRIC - INTERMEDIATE Not ready for Inspection CANCELLED
09/20/2012 ELECTRIC - INTERMEDIATE Partial Approval OK WALLS 4100.5 41018 40039A 400-40044
09/14/2012 ELECTRIC - INTERMEDIATE Partial Approval OK WALLS -30177 30179 30180 30195 30207 30156 30162 30151 30152 FOR PR LOCATIONS
09/12/2012 ELECTRIC - INTERMEDIATE Partial Approval 1. ELEVATOR ELETRIC ROOM MAINTAIN WORKING SPACE CLEARANCES 110.26 (A)(1) TABLE CONDITION 3
09/06/2012 ELECTRIC - INTERMEDIATE Partial Approval CRITICAL POWER HARD PIPED ROOM # 3232,3253,3253A, 3252, NORMAL POWER MC PACUWALLS 3246,3242,3233,3251,3245,3241
09/05/2012 ELECTRIC - INTERMEDIATE Partial Approval ROOMS 30248, 30220, 30225, 30273, 30272, 30293, 30275, 30277
09/04/2012 ELECTRIC - INTERMEDIATE Partial Approval NO INSPECTION ROOM 20408, 20312, 20368, 20363 WEST WALL
08/31/2012 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
08/30/2012 ELECTRIC - INTERMEDIATE Partial Approval ROOMS 20423A,20419,20420,20409,20383A,20365,20347,20348,20349,20361,20392,20389,20485,20484,20483,20447,20481,20482,20350,20358,20359,20345
08/29/2012 ELECTRIC - INTERMEDIATE Partial Approval ROOMS PR.11. 1 THRU 8
CORRIDORS 20492 AND 20360
COLUMNS #1B,1D,1C,1F,1H
08/27/2012 ELECTRIC - INTERMEDIATE Partial Approval 1. p.r. 9-10, 12-21
2. rms. 20364, 20347,20345, 20367, 20366, 20365, 20423a
3. soffits 20312, 20355,2;circles,20346,20367.
08/24/2012 ELECTRIC - INTERMEDIATE Partial Approval 1. REINSPECT MC CABLE CFR CIRCUITS IN CONDUIT
2. PACU 7-15, 16-20, 21-24, 1-6
3. PEDS 1-6
4. EQUIPMENT ROOM 20447
5. 20450 CORIDOR 20463
08/23/2012 ELECTRIC - INTERMEDIATE Partial Approval OK WALLS ROOMS 20527, 20542, 20505, COLUMNS 20528A, 30163-30169, 30222,30313,30316,30317
* PACU UNITS BEING REPIPED PER 517.30(C)(3)
08/17/2012 ELECTRIC - INTERMEDIATE Partial Approval MEET WITH ENGINEER TO DISCUSS ELECTRICAL ROOMS. IT WAS DETERMINED TO ADD DOORS
OK WALLS PR 6-20
08/16/2012 ELECTRIC - INTERMEDIATE Partial Approval FINISH VDV ROOM 20382
OK WALLS ROOMS PACU 1-6 (PEDS) PR1-5 20356, 20383A, PR21
08/14/2012 ELECTRIC - INTERMEDIATE Partial Approval OK SOUTH AND WEST EXTERIOR WALLS RM 50000
08/13/2012 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
08/10/2012 ELECTRIC - INTERMEDIATE Partial Approval OK WALL 20385, 20407-20410, 204017-204120, 20405, 20413
PACU UNITS #10-20, #1-6
08/02/2012 ELECTRIC - INTERMEDIATE Partial Approval OK RECESSED CANS SOFFITTS 20404,20414, 16004B
OK WALLS 16003 NORTH AND WEST
VDV CABLING TO BE AS PER 725.3 AND 8, 760.3 AND 24, 800.3 AND 24
08/01/2012 ELECTRIC - INTERMEDIATE Partial Approval PLEASE VERIFY EGRESS LIGHTING FOR ROOMS 20468, 20469, 30293, 30294
PLEASE VERIFY ADEQUATE LIGHTING FRO EGRESS ROOM 30316, 30317,
OK WALLS ROOMS 30234, 30237-40, 30243, 30247-50, 30300-30305, 30301A, 30306, 30312, 30315, 30285, 30287, 20366, 16324-16328
07/26/2012 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
NOTE STRAIGHT PULL IN BOXES 3/4 28 ALSO
DETAIL 276.32 66.32
OK WALLS ROOMS 30214-30219 30223 30289 30292 30294 30295
07/23/2012 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
RM 50,000 WEST EQUIPMENT PLATFORM LIGHTING NORTH SOUTH AND WEST WALLS PENHOUSE OK
07/19/2012 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK COLUMN 1G, 1H, 1C, 2A
OK WALLS ROOMS 11169 (SOUTH), 16003 (EAST, 16005 (NORTH)
07/18/2012 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
07/16/2012 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
07/10/2012 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
07/06/2012 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
07/03/2012 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
06/27/2012 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
05/10/2012 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) NORTH OUTSIDE WALL 5 LIGHTS OK