Permit: T11CM03694

Parcel: 12511054A

Inspection Status: Denied

Inspection History: FIRE - FINAL

Permit Number - T11CM03694

Inspection Description - FIRE - FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
12/08/2011 FIRE - FINAL Denied Change front cover sheet install sprinklers or remove from cover sheet.
12/08/2011 FIRE - FINAL Approved REVISION TO COVER SHEET SHOWING NO SPRINKLERS OK
12/05/2011 FIRE - FINAL Denied 1. Plans on cover sheet state building is sprinklered when it is not, need to have cover changed and re-stamped showing no sprinklers or install sprinkler per approved plans.
2. 2nd exit door needs a thumb style turn lock to open door.
3. Front main entrance door shall be label with the following "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED" 1 inch lettering on a contrasting background.