Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/23/2012 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 02/17/2012 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED BUSHING ON PVC FITTING 352.46 AND 300.4 2) CLEAN SURFACE UNDER LUG 250.12 AND NO SHEET METAL SCREWS 250.8, JUNCTION BOX, METER SOCKET AND A/C DISCONNECT 3) NOT 65A PROTECTION AT SUB PANEL, VERIFY LOADS 690.64 (B) |
|
| 02/08/2012 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* | |
| 02/06/2012 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELLED BY CONTR. |
|
| 02/02/2012 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 01/26/2012 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WIRE SIZES DO NOT MATCH PLAN 2) NEED TO INSPECT IN MAIN 4-METER SES, CONTRACTOR TO OPEN 3) IS THIS A LINE SIDE TAP ?, PLAN DOES NOT INDICATE 4) REVISE PLAN, BE MORE SPECIFIC |