Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T11CM03682

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
01/20/2012 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
01/12/2012 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK ELECTRIC ABOVE CEILING
01/10/2012 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) SUPPORT PER 300.11 INDEPENDENT 330.30
2) SECURELY ATTACH FIXTURES TO GRID 410.16
3) BOX OVER FILLED
4) PLEASE VERIFY 22K RATING ON SUB PANEL BUSS-BREAKERS ARE
5) CANNOT TAPE A #12 GREEN CONDUCTOR RED
6) TIGHTEN LOOSE TERMINATIONS
7) REMOVE MAIN BONDING JUMPER
8) VERIFY DERATING PER 310.15
9) IDENTIFY GROUNDED CONDUCTOR AT SERVICE 200.6