Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/20/2012 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 01/12/2012 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK ELECTRIC ABOVE CEILING |
|
| 01/10/2012 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) SUPPORT PER 300.11 INDEPENDENT 330.30 2) SECURELY ATTACH FIXTURES TO GRID 410.16 3) BOX OVER FILLED 4) PLEASE VERIFY 22K RATING ON SUB PANEL BUSS-BREAKERS ARE 5) CANNOT TAPE A #12 GREEN CONDUCTOR RED 6) TIGHTEN LOOSE TERMINATIONS 7) REMOVE MAIN BONDING JUMPER 8) VERIFY DERATING PER 310.15 9) IDENTIFY GROUNDED CONDUCTOR AT SERVICE 200.6 |