Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
01/20/2012 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
01/12/2012 ELECTRIC - INTERMEDIATE Cancelled IVRS - RI canceled
12/20/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK WALLS AND HARD LIDS
2) CHECK JUNCTION BOXES ON ABOVE CEILING
3) RECEIVED REFEE CHECK #1275 FOR $82.50
12/19/2011 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspection
1) JUNCTION BOXES TO BE ACCESSIBLE
2) FITTINGS LOOSE
3) NEED M/C PROTECTION AT SHALLOW STUDS
4) FINISH SUPPORTING AND SECURING M/C CABLE PER NEC
5) PAY REINSPECTION FEE BEFORE NEXT INSPECTION
12/16/2011 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) USE APPROVED FITTINGS FOR M/C
2) PROTECT M/C ACROSS SHALLOW STUDS
3) TIGHTEN LOOSE FITTINGS
4) SUPPORT M/C WITHIN 12" OF BOXES
5) M/C TO BE 1 1/4" FROM STUD EDGE
6) A REINSPECTION FEE MAYBE CHARGED FOR INCOMPLETE INSPECTIONS
12/15/2011 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CANNOT SECURE M/C TO DRYWALL
2) SECURE M/C WITHIN 12" OF BOXES 33?.30
3) TIGHTEN LOOSE FITTINGS
4) PROTECT M/C AT TOP PLATE
5) SUPPORT VDV CABLES IN WALLS 725.8