Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T11CM03682
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/20/2012 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
01/12/2012 | ELECTRIC - INTERMEDIATE | Cancelled | IVRS - RI canceled | |
12/20/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS AND HARD LIDS 2) CHECK JUNCTION BOXES ON ABOVE CEILING 3) RECEIVED REFEE CHECK #1275 FOR $82.50 |
|
12/19/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspection 1) JUNCTION BOXES TO BE ACCESSIBLE 2) FITTINGS LOOSE 3) NEED M/C PROTECTION AT SHALLOW STUDS 4) FINISH SUPPORTING AND SECURING M/C CABLE PER NEC 5) PAY REINSPECTION FEE BEFORE NEXT INSPECTION |
|
12/16/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) USE APPROVED FITTINGS FOR M/C 2) PROTECT M/C ACROSS SHALLOW STUDS 3) TIGHTEN LOOSE FITTINGS 4) SUPPORT M/C WITHIN 12" OF BOXES 5) M/C TO BE 1 1/4" FROM STUD EDGE 6) A REINSPECTION FEE MAYBE CHARGED FOR INCOMPLETE INSPECTIONS |
|
12/15/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CANNOT SECURE M/C TO DRYWALL 2) SECURE M/C WITHIN 12" OF BOXES 33?.30 3) TIGHTEN LOOSE FITTINGS 4) PROTECT M/C AT TOP PLATE 5) SUPPORT VDV CABLES IN WALLS 725.8 |