Permit: T11CM03634

Parcel: 11205030B

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
10/31/2012 FIRE - FINAL Approved
10/30/2012 FIRE - FINAL Denied
10/11/2012 FIRE - FINAL Not ready for Inspection WANTED INFO ON GETTING PARTIALS FOR BUILDING TO RENT OUT. The following was info was given:
1. Address number on each apartment 3" and building number on buildings 12" main address number post on building street side 12"
2. Construction fencing down around areas that will be rented out so not blocking access to or from apartments.
3. All sidewalks in the partial approvals areas done before renting.
4. Smoke detectors installed and tested in partial areas.
5. Sprinkler finals done and sub-contractors sprinkler permit done.
6. Fire extinguishers installed outside in cabinets posted every 75 feet travel distance 2A-20BC or each apartment having its own fire extinguisher installed in the kitchen area minimum rating 1A-10BC