Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/17/2012 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 01/10/2012 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BRACED PANEL NAILING 6' ON CENTER ALL EDGES 12" IN FIELD 2) MISSING DBL TOP PLATES BEARING WALLS. INSTALL PLATES OR STUD UNDER TRUSSES WITHIN 1 1/2" 3) X BRACE GABLE END 4) PROVIDE 2-2 X 8 BOX HEADERS PER PLAN 5) PROVIDE 2 ABS PER BRACED PANEL 6) PROVIDE SAFE ACCESS TO ROOF |