Permit: T11CM03612

Parcel: 103110610

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
12/30/2011 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
12/23/2011 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) FLUE PIPE JOINTS ARE TO BE PROPERLY FITTED, TWIST AND SNAP, DO NOT USE SCREWS ON B-VENT CONNECTIONS
2) PROVIDE MIN 1" CLEARENCE TO COMBUSTIONS FROM B-VENT PER INSTALL INSTRUCTIONS
3) ALL OTHER CORRECTINS HAVE BEEN MADE
4) ROOF JACK NOT PROPERLY FITTED, MAKE LEAK FREE
12/19/2011 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
12/16/2011 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) SEE NOTE NUMBER 7 FROM 11/30/11
2) UV PROTECTION TO BE CONTINOUS AROUND ARMAFLEX
3) SECTIONS OF ARMAFLEX ARE SPLITTING OPEN
4) CONTRACTOR TO PAY REINSPECTION FEE
11/30/2011 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) ROOF TOP INSULATION TO BE INSTALLED PER MANUFACTURES SPEC. IE.........TAPE AND LAGGING ADHESIVE. COMPLETE UV PROTECTION ON ROOF
2) INSULATION IN WATER HEATER CLOSET REQUIRES LAGGING ADHESIVE AND TAPE
3) DBL WALL VENT REQUIRES 1" FROM COMBUSTIBLES
4) T & P ? DRAINS TO TERMINATE OUTSIDE AND POINTING DOWN
5) WATER HEATER GAS VALVE TO BE ACCESSIBLE AND FLEX TO LONG
6) CONTINUED NOT READYS WILL RESULT IN REINSPECTION FEE. NOTE: MOVING WATER HEATER TO OUTSIDE REQUIRES A SEPERATE PERMIT
7) WATER HEATER VENT TO EXTEND 5' ABOVE WATER HEATER