Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/03/2012 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 05/01/2012 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PLEASE CALL IN AND HAVE APPROVED, ALL REQUIRED INSPECTIONS PRIOR TO CALLING FINAL 2) REVIEWED FINAL REQUIREMENT WITH OWNER AND RON BOOSE |
|
| 04/27/2012 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) EACH WATER SUPPLIED DEVICE REQUIRES BACKFLOW PROTECTION, NO SPLITTING DOWNSTREAM OF DEVICE 2) INDIRECT WASTE PIPING TO HAVE PRIMER AND SOLVENT CEMENT, THERE IS NO ONE STEP FOR PVC 3) INDIRECT WASTE PIPING REQUIRES 1" MINIMUM AIR GAP 4) METHOD OF STERILIZATION, CLEAN BACTERIA REPORT AND BACKFLOW CERTIFICATION |
|
| 04/26/2012 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) SUPPORT MIXING VALVES UNDER LAVATORIES 2) INSTALL CP?? COVERS AND FINISH CLEANOUT IN WOMENS HC STALL. EACH WATER SUPPLIED DEVICE REQUIRES BACKFLOW PROTECTION 3) PLASTIC HOSE IS NOT APPROVED DRAINAGE MATERIAL 4) INSPECTION STOPPED 5) PLEASE HAVE PLUMBER ON SITE AT NEXT INSPECTION |
|
| 04/25/2012 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* |