Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
05/03/2012 PLUMBING - FINAL Approved IVRS - Inspection :*
05/01/2012 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) PLEASE CALL IN AND HAVE APPROVED, ALL REQUIRED INSPECTIONS PRIOR TO CALLING FINAL
2) REVIEWED FINAL REQUIREMENT WITH OWNER AND RON BOOSE
04/27/2012 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) EACH WATER SUPPLIED DEVICE REQUIRES BACKFLOW PROTECTION, NO SPLITTING DOWNSTREAM OF DEVICE
2) INDIRECT WASTE PIPING TO HAVE PRIMER AND SOLVENT CEMENT, THERE IS NO ONE STEP FOR PVC
3) INDIRECT WASTE PIPING REQUIRES 1" MINIMUM AIR GAP
4) METHOD OF STERILIZATION, CLEAN BACTERIA REPORT AND BACKFLOW CERTIFICATION
04/26/2012 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) SUPPORT MIXING VALVES UNDER LAVATORIES
2) INSTALL CP?? COVERS AND FINISH CLEANOUT IN WOMENS HC STALL. EACH WATER SUPPLIED DEVICE REQUIRES BACKFLOW PROTECTION
3) PLASTIC HOSE IS NOT APPROVED DRAINAGE MATERIAL
4) INSPECTION STOPPED
5) PLEASE HAVE PLUMBER ON SITE AT NEXT INSPECTION
04/25/2012 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*