Permit: T11CM03590

Parcel: 107051030

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/01/2012 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/30/2012 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) KITCHEN EAST EM LIGHT 700.12 (F) ON AREA SERVED
2) METAL PARTS ON BATHROOM HEATER ARE NOT BONDED
3) FINISH HOOD DISCONNECT LABELING
4) ALL KITCHEN RECEPTS 125V, 15-20 AMP TO BE GDCI 210.8
04/27/2012 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
04/26/2012 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
ROOF:
1) HOOD DISCONNECT MISSING LOCK NUT, LABEL DISCONNECT AND CORDS NOT ALLOWED FOR PERMANENT WIRING 400.7 & 8
2) FINISH 1, 2, 8 AND BATHROOM HEATER
04/24/2012 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) BATHROOM HEATERS-VERIFY MAKE UP AND LISTING
2) RECEPT COVERS TO BE PER 406.8
3) MAINTAIN WORKING CLEARANCES 110.26 (A/C DISCONNECT)
4) LABEL DISCONNECTING MEANS A/C PERMANENT LABELS
5) SUPPORT SEAL TITE-SPLIT UNITS
6) FINISH HOOD SYSTEM
7) FINISH #1,2,4,7 AND 8 PREVIOUS ITEMS
04/16/2012 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ALL KITCHEN 15 & 20 AMP 120 VOLT RECEPTS TO BE GFCI PROTECTED 2?0.8
2) BOXES MORE THAN 1/4" 814.20-LIGHT BOXES ALSO
3) PLEASE VERIFY LISTING LABELING OF ALL KITCHEN EQUIPMENT
4) PROVIDE PHYSICAL PROTECTION FOR M/C CABLES AT BARS
5) PLEASE PROVIDE PAPERWORK DIMMER DETERIORATING IN MULTI GANG BOXES
6) WET LOCATION COVERS NEEDED OUTSIDE BAR
7) RECEPT COVER METAL TO BE 406.3
8) LABEL ALL BREAKERS AND MUST MATCH PANEL MANUFACTURE FOR BREAKERS
9) INSPECTION STOPPED