Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/24/2012 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 02/22/2012 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SERVICE TO HAVE 2 GROUND RODS 2) SUB PANEL NEUTRAL NOT TO BE BONDED 3) SOLAR DISCONNECT CONNECTOR LOOSE 4) SUB PANEL AND MAIN HOUSE PANEL TO BE GROUNDED, TO HAVE 1 GROUNDING SYSTEM 5) PIPE GOING TO ROOF SOLAR PANELS TO BE 3/4 |