Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/17/2012 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 01/13/2012 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) CHECK ON FINAL |
|
| 01/12/2012 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) PROVIDE PROPER SUPPORT FOR FLEX DUCT SUPPORT NOT TO EXCEED 5'; DO NOT USE OTHER TRADES FOR DUCT SUPPORT (CONDUIT, WATER LINES, ECT...) 2) COMPLETE INSULATION OF DUCT, END CAPS, BRANCH TAPS ECT... 3) COMPLETE SESMIC RESTRAINTS TO ALL T-BAR GRILLS |