Permit: T11CM03501

Parcel: 13507451C


Addresses:

1851 S PANTANO RD


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T11CM03501

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/29/2013 FIRE - FINAL Approved
01/16/2013 FIRE - FINAL Partial Approval Wire all dry powder spray booths to the monitoring system X 3
Install FD key system to all access gates
Approved plans shall be changed showing no fire alarm is required.
Chain locks or approved locking devices needed on all sprinkler valves for spray booths X 3
01/14/2013 FIRE - FINAL Not ready for Inspection
12/18/2012 FIRE - FINAL Denied Need to have approved plans reflect that no alarm system will be installed Per letter from Advantech engineering dated December 14, 2012.
12/17/2012 FIRE - FINAL Denied NEED SUB SPRINKLER CONTRACTOR CALL IN 4 OPEN SPRINKLER PERMITS BEFORE CALLING FOR YOUR SPRINKLER FINAL.