Permit: T11CM03476

Parcel: 116154980

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T11CM03476

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/02/2012 ELECTRIC - FINAL Approved
03/01/2012 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) FINISH #1 & 5
02/27/2012 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MISSING LIGHT FIXTURES
2) BOXES MORE THAN 1/4" 314.20
3) MULTI WIRE RECEPTS TO HAVE HANDLE TIES
4) FIRE ALARM ? DOOR WILL NOT FULLY OPEN AT LEAST 90 DEGREE
5) NEED TO SEE MEDICAL EQUIPMENT TO DETERMINE IF HOSPITAL GRADE RECEPTS ARE NEEDED 110.3 (B) AND VERIFY LISTING
6) SUPPORT VDV CABLING IT ROOM
7) MISSING SCREWS RECEPTS COVERS 406.3
8) NEED ROOF ACCESS