Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/02/2012 | ELECTRIC - FINAL | Approved | ||
| 03/01/2012 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) FINISH #1 & 5 |
|
| 02/27/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MISSING LIGHT FIXTURES 2) BOXES MORE THAN 1/4" 314.20 3) MULTI WIRE RECEPTS TO HAVE HANDLE TIES 4) FIRE ALARM ? DOOR WILL NOT FULLY OPEN AT LEAST 90 DEGREE 5) NEED TO SEE MEDICAL EQUIPMENT TO DETERMINE IF HOSPITAL GRADE RECEPTS ARE NEEDED 110.3 (B) AND VERIFY LISTING 6) SUPPORT VDV CABLING IT ROOM 7) MISSING SCREWS RECEPTS COVERS 406.3 8) NEED ROOF ACCESS |