| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/09/2012 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 01/03/2012 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* 1) LABELING PER 690.17-DISC NEXT TO INVERTER 2) MAINTAIN WORKING SPACE 110.26 3) BREAKER NOT SIZED PER 690.64 (B) 4) FULLY SEAL ROOF FLASHING FOR SUPPLY POWER |