Permit: T11CM03468

Parcel: 125170430

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T11CM03468

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/09/2012 BUILDING - FINAL Approved IVRS - Inspection :*
01/03/2012 BUILDING - FINAL Partial Approval IVRS - Inspection :*
1) LABELING PER 690.17-DISC NEXT TO INVERTER
2) MAINTAIN WORKING SPACE 110.26
3) BREAKER NOT SIZED PER 690.64 (B)
4) FULLY SEAL ROOF FLASHING FOR SUPPLY POWER