Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/29/2011 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/20/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MISSING DEVICE COVERS
2) NEED ALL SCREWS IN PANEL COVER
3) NEED REVISED PANEL DIRECTORIES
4) NEUTRAL CONDUCTOR IN RACEWAY TO BE WHITE ENTIRE LENGTH 200.6
5) PLANS DO NOT SHOW NEW LIGHTS
6) BOXES MORE THAN 1/4" 314.20
7) USE APPROVED HARDWARE FOR DEVICES-NOT DRYWALL SCREWS
8) OPEN 8' STRIP LIGHTS (NEW) TO INSPECT