Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/29/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/20/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MISSING DEVICE COVERS 2) NEED ALL SCREWS IN PANEL COVER 3) NEED REVISED PANEL DIRECTORIES 4) NEUTRAL CONDUCTOR IN RACEWAY TO BE WHITE ENTIRE LENGTH 200.6 5) PLANS DO NOT SHOW NEW LIGHTS 6) BOXES MORE THAN 1/4" 314.20 7) USE APPROVED HARDWARE FOR DEVICES-NOT DRYWALL SCREWS 8) OPEN 8' STRIP LIGHTS (NEW) TO INSPECT |