Permit: T11CM03445

Parcel: 10605096B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/10/2012 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/09/2012 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SEAL CONDUIT INTERIORS PER 300.7
2) TIGHTEN LOOSE FITTINGS
3) PROPERLY GROUND JUCTION BOX-ONLY ONE CONDUCTOR TO SCREW TERMINAL
4) USE APPROVED HARDWIRE FOR COVERS
ROOF:
1) NON WEATHER PROOF DISCONNECT IN DETERIORATED CONDITION, ALSO CONDUCTORS AND SEAL TIGHT DETERIORATED