Permit: T11CM03423

Parcel: 11310114B


Addresses:

2575 N CAMPBELL AV

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
03/08/2012 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
02/21/2012 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) WAITING FOR LETTERS FROM ENGINEER
2) INSTALL CEILING TILES AT YOUR OWN RISK
3) WILL CHECK AT FINAL
02/17/2012 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) DUCT MATERIAL, FASTENERS AND HANGERS NOT PER PLAN
2) FLEX DUCT NOT INSTALLED PER PLANS-USE VERTICAL ONLY
3) FLEX DUCT LENGTH NOT PER PLANS
4) BRANCH FITTINGS NOT PER PLANS
5) DUCT NOT SEALED PER PLANS
6) EXHAUST NOT PER PLANS