Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/08/2012 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 02/21/2012 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) WAITING FOR LETTERS FROM ENGINEER 2) INSTALL CEILING TILES AT YOUR OWN RISK 3) WILL CHECK AT FINAL |
|
| 02/17/2012 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DUCT MATERIAL, FASTENERS AND HANGERS NOT PER PLAN 2) FLEX DUCT NOT INSTALLED PER PLANS-USE VERTICAL ONLY 3) FLEX DUCT LENGTH NOT PER PLANS 4) BRANCH FITTINGS NOT PER PLANS 5) DUCT NOT SEALED PER PLANS 6) EXHAUST NOT PER PLANS |