Permit: T11CM03423

Parcel: 11310114B


Addresses:

2575 N CAMPBELL AV

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
03/09/2012 PLUMBING - FINAL Approved IVRS - Inspection :*
03/05/2012 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) SUPPORT BACKFLOW DEVICE UNDER SODA MACHINE-REINSTALL SO AS TO NOT INTERFERE WITH THE OTHER DEVICE
2) EXTEND PVC DRAIN TO SODA MACHINE AT CANOPY DRAIN; ABS NOT PERMITTED IN EXPOSED EXTERIOR LOCATIONS
3) EXTEND SODA MACHINE DRAIN TO FUNNEL
4) PROVIDE BACKFLOW FOR ICE TEA BREWER
5) CONNECT ALL EQUIPMENT
6) UNABLE TO LOCATE SHUT OFF VALVE, EXPANSION TANK, VACUUM RELIEF FOR WATER HEATER
7) VENT COLLAR TO VENT CONNECTION NOT MADE UP PROPERLY
8) REQUIRE 1" CLEARANCE TO COMBUSTIBLES FROM B-VENT
02/28/2012 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
02/23/2012 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*