Permit: T11CM03423

Parcel: 11310114B


Addresses:

2575 N CAMPBELL AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/07/2012 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/06/2012 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) FINISH OUTSIDE LIGHTS (NOTE: M/C TO TERMINATE IN A FITTING)
2) FINISH CIRCUIT DIRECTORIES #3 PREVIOUS
3) SEALING FOR WALK IN TO BE NON COMBUSTIBLE/FLAMABLE (DUCT SEAL OK)
4) GROUND JUNCTION BOXES
5) MENU BOARDS NOT INSTALLED #9 PREVIOUS
6) FINISH ROOF LABELING-PERMANENT #2 ROOF
03/05/2012 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) PROTECT CONDUCTOR 350.46 AND 300.4
2) CLEAN EXCESS FOREIGN MATERIAL AND DIRT FROM BOTTOM OF PANELS 110.12
3) NEED CIRCUIT DIRECTORIES PER 408.3
4) BOXES MORE THAN 1/4" BOX TO SURFACE 314.20
5) LIGHT FIXTURES TO HAVE DISCONNECTING MEANS 410.73 (G)
6) FILL UNUSED OPENINGS IN BOXES-NOT OLD FITTINGS
7) SEAL ENTRANCES TO WALK IN BOX 300.7
8) EM LIGHTING TO BE ON CIRCUIT FOR AREA SERVED 700.12 (F)
9) MENU BOARDS NOT INSTALLED AT THIS TIME
ROOM:
1) SUPPORT SEAL TITE AND CONDUITS PER CODES
2) LABEL DISCONNECTS