Permit: T11CM03423

Parcel: 11310114B


Addresses:

2575 N CAMPBELL AV

Inspection Status: Approved

Inspection History: ELECTRIC - PROGRESS

Date Description Inspector Results Comments
02/24/2012 ELECTRIC - PROGRESS Approved IVRS - Inspection :*
02/23/2012 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) GEC NOT TERMINATED
2) NO FUSES/R-PINS
3) BOND WATER/GAS, BLDG STEEL
4) THIS INSPECTION WAS FOR SERVICE EQUIPMENT-SEE REVISED PLAN
02/21/2012 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
02/17/2012 ELECTRIC - PROGRESS Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
02/08/2012 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) SECURE VDV CAABLEING #5 PREVIOUS ITEM
2) FINISH & NOTE #3,4 & 7
OK WALLS & HARD LIDS DINNING 101 AFTER CORRETION FOR VDV CABLES AND BATHROOM M/C
02/06/2012 ELECTRIC - PROGRESS Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) LOOSE FITTING & STRAP FEEDER RACE WAYS
2) FILL UNUSED OPENINGS IN PANEL
3) NOTE 352.46 & 300.4 MAY APPLY
4) SECURE M/C CABLE WITHIN 12" OF BOXES 334.30
5) SECURE VDV IN WALL 725.8 ,800.24 & PROTECT CABLE FROM SHARP METAL EDGES
6) PROTECT M/C IN SHALLOW STUPS
7) BOX OVER FILLED