Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - PROGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/24/2012 | ELECTRIC - PROGRESS | Approved | IVRS - Inspection :* | |
| 02/23/2012 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) GEC NOT TERMINATED 2) NO FUSES/R-PINS 3) BOND WATER/GAS, BLDG STEEL 4) THIS INSPECTION WAS FOR SERVICE EQUIPMENT-SEE REVISED PLAN |
|
| 02/21/2012 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 02/17/2012 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 02/08/2012 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) SECURE VDV CAABLEING #5 PREVIOUS ITEM 2) FINISH & NOTE #3,4 & 7 OK WALLS & HARD LIDS DINNING 101 AFTER CORRETION FOR VDV CABLES AND BATHROOM M/C |
|
| 02/06/2012 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) LOOSE FITTING & STRAP FEEDER RACE WAYS 2) FILL UNUSED OPENINGS IN PANEL 3) NOTE 352.46 & 300.4 MAY APPLY 4) SECURE M/C CABLE WITHIN 12" OF BOXES 334.30 5) SECURE VDV IN WALL 725.8 ,800.24 & PROTECT CABLE FROM SHARP METAL EDGES 6) PROTECT M/C IN SHALLOW STUPS 7) BOX OVER FILLED |