Permit: T11CM03423

Parcel: 11310114B


Addresses:

2575 N CAMPBELL AV

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
02/21/2012 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
02/17/2012 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) SECURE M/C 330.30 6', 12" BOXES-CEILING AND COUNTER WALL
2) BOXES OVERFILLED
3) CONTRACTOR TO BE LISTED
4) SECURE VDV CABLING PER 725.87 AND 800.24
5) CANNOT USE DRYWALL SCREWS WITH ELECTRIC BOXES
6) 314.20 WILL APPLY
02/08/2012 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
02/06/2012 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*