Permit: T11CM03397

Parcel: 120060840


Addresses:

113 E LINCOLN ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
12/30/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
12/20/2011 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ELECTRIC ROOF JACK NOT SEALED
2) PROVIDE APPROVED ELECTRIC FITTINGS ON SEAL TITE
3) PROVIDE ROOF JACK AT ELECTRIC (T-STAT) PENETRATION
4) PROVIDE APPROVED ENCLOSURE FOR OR REMOVE BARE WIRING ON ROOF
5) PROVIDE P-TRAP AT CONDENSATE DRAIN PIPING
6) ALL PVC JOINTS AND FITTINGS ARE TO BE PRIMED PRIOR TO GLUE, PRIMER IS TO BE PURPLE IN COLOR PER UPC
7) ALL PVC EXPOSED TO DAY LIGHT IS TO BE COATED FOR U.V. PROTECTION
8) ALL CONDUIT (INCLUDING FLEXABLE) IS TO BE BLOCKED UP OFF OF ROOF
12/09/2011 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE LADDER FOR ROOF ACCESS