Permit: T11CM03397

Parcel: 120060840


Addresses:

113 E LINCOLN ST

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
12/09/2011 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
10/28/2011 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PANEL NOT GROUNDED
2) MISSING DEAD FRONT. PROVIDE LISTED DEADFRONT
3) WHITE 30 AMP HOT LEAD MUST BE BLACK OR RED (TAPE OK)
4) MISSING WATER HEATER. PROVIDE PERMIT FOR REPLACEMENT
5) PROVIDE WEATHERED FIXTURE REAR EXIT DOOR
6) SMOKE ALARM BEDROOMS AND HALLWAYS
7) ALL ADDITIONS SHOULD BE ON RECORD
8) NOTES 1, 2, 3, 5 & 6 FOR POWER