Inspection History Details
Inspection Status: Approved
Inspection History: OUTDOOR LIGHTING FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/06/2012 | OUTDOOR LIGHTING FINAL | Approved | IVRS - Inspection :* | |
| 01/04/2012 | OUTDOOR LIGHTING FINAL | Partial Approval | IVRS - Inspection :* 1) EM LIGHTING TO BE PER 700.12 (F) 2) SEAL UNUSED CONDUIT OPENINGS 3) SUPPORT EMT ABOVE PANEL 3' 4) RECEPT COVERS TO BE PER 406.8 5) NEED ARC FLASH LABELING 6) CANNOT STACK LUGS AND MOVE OFF OF ISOLATION STRAP |