Permit: T11CM03352

Parcel: 11616302A

Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Date Description Inspector Results Comments
05/10/2012 ELECTRIC - UFER Approved IVRS - Inspection :*
04/16/2012 ELECTRIC - UFER Partial Approval IVRS - Inspection :*
1) OK 2 GROUND RODS AND #2 COPPER
2) BOND BOTTOM REBAR 250.6
3) OK TO POUR
04/12/2012 ELECTRIC - UFER Not ready for Inspection IVRS - Inspection :*
1) OK PVC CONDUITS TO SES
2) OK 2 VAULTS
NOTE: 408.3 WILL APPLY
03/20/2012 ELECTRIC - UFER Partial Approval IVRS - Inspection :*
1) OK #2 SUPLIMENTAL ELECTRODE CONDUCTORS 8 POLES
03/19/2012 ELECTRIC - UFER Not ready for Inspection IVRS - Inspection :*