Permit: T11CM03348

Parcel: 122030100


Addresses:

2235 N MADELYN AV

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
11/08/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
10/28/2011 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) TIGHTEN ELECTRICAL CONNECTION TO TOP OF FAN COIL
2) REMOVE 1/4" TUBING FROM INSIDE DRAIN HOSE FROM HUMIDIFIER AND CONDENSATE PUMP
3) ELECTRIC CONNECTION FROM DISCONNECT IS ALSO LOOSE
4) CONDENSATE CANNOT TERMINATE INTO A SEWER VENT
5) DO NOT USE PLASTIC HOSE OUTDOOR
6) SUPPORT REFRIDGERATION LINE ON ROOF
7) USE REDWOOD OR PRESSURE TREATED WOOD FOR BLOCKING CONDUITS AND LINE SET
8) YOU CANNOT HAVE CARAFLEX CONDUIT GLUED INTO A PLASTIC LB
9) HOW IS CARAFLEX CONDUIT CONNECTED TO PVC INSIDE EAVE ?
10) USE ONLY UL LISTED LINE SET TAPE AT CONDENSOR
11) YOU CAN ALSO USE 10 MIL PIPE WRAP TAPE UPC LISTED