Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/08/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 10/28/2011 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) TIGHTEN ELECTRICAL CONNECTION TO TOP OF FAN COIL 2) REMOVE 1/4" TUBING FROM INSIDE DRAIN HOSE FROM HUMIDIFIER AND CONDENSATE PUMP 3) ELECTRIC CONNECTION FROM DISCONNECT IS ALSO LOOSE 4) CONDENSATE CANNOT TERMINATE INTO A SEWER VENT 5) DO NOT USE PLASTIC HOSE OUTDOOR 6) SUPPORT REFRIDGERATION LINE ON ROOF 7) USE REDWOOD OR PRESSURE TREATED WOOD FOR BLOCKING CONDUITS AND LINE SET 8) YOU CANNOT HAVE CARAFLEX CONDUIT GLUED INTO A PLASTIC LB 9) HOW IS CARAFLEX CONDUIT CONNECTED TO PVC INSIDE EAVE ? 10) USE ONLY UL LISTED LINE SET TAPE AT CONDENSOR 11) YOU CAN ALSO USE 10 MIL PIPE WRAP TAPE UPC LISTED |