Permit: T11CM03273

Parcel: 134233580


Addresses:

6342 E MALVERN ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/28/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
10/25/2011 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) CONDENSATE CANNOT TERMINATE INTO SEWER VENT
2) PROVIDE MINIMUM 1/8" PER FT SLOPE ON DRAIN LINE
3) 1/2" GAS PIPE IS NOT ADEQUATE FOR 120,000 BTU FURNACE EXTEND 3/4" PIPE FROM WATEER HEATER ROOM ALL THE WAY TO FURNACE ON ROOF