Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/28/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 10/25/2011 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) CONDENSATE CANNOT TERMINATE INTO SEWER VENT 2) PROVIDE MINIMUM 1/8" PER FT SLOPE ON DRAIN LINE 3) 1/2" GAS PIPE IS NOT ADEQUATE FOR 120,000 BTU FURNACE EXTEND 3/4" PIPE FROM WATEER HEATER ROOM ALL THE WAY TO FURNACE ON ROOF |