Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE RELOCATION
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/22/2011 | ELECTRIC - SERVICE RELOCATION | Approved | IVRS - Inspection :* | |
| 12/21/2011 | ELECTRIC - SERVICE RELOCATION | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) UNDERSIZED OVERHEAD CONDUCTORS (1/0 ALUM) FOR 200 AMP PANEL |
|
| 12/20/2011 | ELECTRIC - SERVICE RELOCATION | Not ready for Inspection | 1) PROVIDE 24" CONDUCTORS AT WEATHER HEAD 2) METAL ADDRESS TAG 3) PROVIDE SECONDARY CLAMP ? AT RISER 4) BRACE RISER OVER 36" ROOF TOP |