Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/30/2011 | FIRE SPKLR - FINAL | Approved | IVRS - Inspection :* | |
| 12/28/2011 | FIRE SPKLR - FINAL | Not ready for Inspection | ||
| 12/27/2011 | FIRE SPKLR - FINAL | Not ready for Inspection | 1 painted sprinkler head. | |
| 12/21/2011 | FIRE SPKLR - FINAL | Not ready for Inspection | 1. Hood #3 needs accurate floor plans of appliances under the hood. 2. Exhaust fan on roof the electrical wiring needs to be water tight. 3. Various painted heads 4. 5 year check valve test required. 5. Missing sprinkler wrench 6. Must have ten feet of seperation from back of building to sheds or a 2 hour fire wall. |