Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - PROGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/07/2012 | PLUMBING - PROGRESS | Approved | IVRS - Inspection :* | |
| 02/06/2012 | PLUMBING - PROGRESS | Not ready for Inspection | IVRS - Inspection :* | |
| 02/02/2012 | PLUMBING - PROGRESS | Not ready for Inspection | IVRS - Inspection :* | |
| 01/30/2012 | PLUMBING - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 01/27/2012 | PLUMBING - PROGRESS | Not ready for Inspection | IVRS - Inspection :* | |
| 01/26/2012 | PLUMBING - PROGRESS | Not ready for Inspection | IVRS - Inspection :* | |
| 01/23/2012 | PLUMBING - PROGRESS | Not ready for Inspection | IVRS - Inspection :* 1) COMPLETE ABOVE CEILING PIPE SUPPORTS AND PIPE INSULATION 2) REPLACE ANY MISSING OR DAMAGED SUPPORTS IN CEILING AND ON ROOF 3) RECIRC HW REQUIRES 1" THICK INSULATION PER CODE-SEAL JOINTS 4) FOR FINAL, COMPLETE WORK 5) NOTE: ALL HOSE BIBS REQUIRE VACUUM BREAKERS-BREAK OFF SCREWS 6) NEW LAVATORIES REQUIRE MIXING VALVES-SUPPORT 7) BACKFLOW CERTS, STERILIZATION AND BAR T TEST REQUIRED-BACKFLOW FOR ICE MAKER 8) DRAINS MAY NOT BE RESTRICTED 9) INDIRECT DRAINS MAY NOT COMBINE 10) STRAINERS CLEANOUT PLUG ETC...GRATES 11) LIST NOT COMPLETE |
|
| 12/30/2011 | PLUMBING - PROGRESS | Not ready for Inspection | 1) CORRECT WATER HEATER VENTING-COMPLETE WORK 2) CALL FOR MECHANICAL INSPECTION 04035 AND GAS FINAL 03052 FOR GAS CLEARANCE |
|
| 12/13/2011 | PLUMBING - PROGRESS | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ALL COPPER PIPING SHALL BE DE-BURRIED, RE-DO ANY PIPING THAT HAS NOT BEEN REAMED 2) 1" THICK INSULATION SPECIFIED |