Permit: T11CM03236

Parcel: 12801013B


Addresses:

330 S WILMOT RD

Inspection Status: Approved

Inspection History: PLUMBING - PROGRESS

Date Description Inspector Results Comments
02/07/2012 PLUMBING - PROGRESS Approved IVRS - Inspection :*
02/06/2012 PLUMBING - PROGRESS Not ready for Inspection IVRS - Inspection :*
02/02/2012 PLUMBING - PROGRESS Not ready for Inspection IVRS - Inspection :*
01/30/2012 PLUMBING - PROGRESS Partial Approval IVRS - Inspection :*
01/27/2012 PLUMBING - PROGRESS Not ready for Inspection IVRS - Inspection :*
01/26/2012 PLUMBING - PROGRESS Not ready for Inspection IVRS - Inspection :*
01/23/2012 PLUMBING - PROGRESS Not ready for Inspection IVRS - Inspection :*
1) COMPLETE ABOVE CEILING PIPE SUPPORTS AND PIPE INSULATION
2) REPLACE ANY MISSING OR DAMAGED SUPPORTS IN CEILING AND ON ROOF
3) RECIRC HW REQUIRES 1" THICK INSULATION PER CODE-SEAL JOINTS
4) FOR FINAL, COMPLETE WORK
5) NOTE: ALL HOSE BIBS REQUIRE VACUUM BREAKERS-BREAK OFF SCREWS
6) NEW LAVATORIES REQUIRE MIXING VALVES-SUPPORT
7) BACKFLOW CERTS, STERILIZATION AND BAR T TEST REQUIRED-BACKFLOW FOR ICE MAKER
8) DRAINS MAY NOT BE RESTRICTED
9) INDIRECT DRAINS MAY NOT COMBINE
10) STRAINERS CLEANOUT PLUG ETC...GRATES
11) LIST NOT COMPLETE
12/30/2011 PLUMBING - PROGRESS Not ready for Inspection 1) CORRECT WATER HEATER VENTING-COMPLETE WORK
2) CALL FOR MECHANICAL INSPECTION 04035 AND GAS FINAL 03052 FOR GAS CLEARANCE
12/13/2011 PLUMBING - PROGRESS Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ALL COPPER PIPING SHALL BE DE-BURRIED, RE-DO ANY PIPING THAT HAS NOT BEEN REAMED
2) 1" THICK INSULATION SPECIFIED