Permit: T11CM03236

Parcel: 12801013B


Addresses:

330 S WILMOT RD

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
01/30/2012 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
01/27/2012 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
01/26/2012 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
01/23/2012 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
12/12/2011 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
11/29/2011 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) IN WALLS OK
11/28/2011 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) INSTALL PROPERLY SIZED SUPPORTS ON PIPE INSULATION-SEAL SEAMS
2) SUPPORT ABS IN WALL AND OVER HEAD
3) COMPLETE WORK AT WATER STATION BUFFET
4) 1" FIBERGLASS INSULATION SPECIFIED FOR DOMESTIC HOT
5) DWV TEST OK
11/23/2011 PLUMBING - INTERMEDIATE Not ready for Inspection PROVIDE A TEST ON DWV.
SUPPORT PIPING IN WALLS W/ISOLATION FROM SHARP METAL, S??? RISERS.
SUPPORT OVER HEAD PIPING AT EACH END AND NOT TO EXCEED 4', USE APPROVED SUPPORTS AND SAFETY PLATES.
SECURE DOG EAR ISOLATORS, SWEEPS REQUIRED ON TRAP ARMS.
TEST ON DOMESTIC WATER OK, INSULATE AS SPECIFIED.
IT IS NOT OK TO ONSIDE OR COVER ANY PLUMBING WALLS