Permit: T11CM03236

Parcel: 12801013B


Addresses:

330 S WILMOT RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/06/2012 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/01/2012 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PARKING LOT LIGHTS NOT WORKING, WALL PACKS AND FLOOD LAMPS
2) ROOF GFI'S MISSING
3) EM AND EXITS IN BLDG OK
4) FREEZER FUSES TO SMALL
01/30/2012 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GFI'S MISSING IN KITCHEN 210.8.B.2
2) PANEL SCHEDULE SHOWING EM AND EXIT MISSING
3) FREEZER PENETRATIONS TO BE SEALED
4) MACHINE SCREWS ON OUTLETS NOT SHEET SCREWS OR SHEET METAL SCREWS 406.4.C
5) OUTLETS TO FAR FROM EDGWE 406.4.A
01/23/2012 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*