Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/26/2012 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 01/23/2012 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LIGHT WHIPS OFF GRID 2) LOW VOLTAGE STRAPPED 3) PIPES EMT TO BE REMOVED OR PLUGGED 4) BOX TO BE ANCHORED |
|
| 12/15/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection : 1) FRONT AREA TEE BAR AND HARD LIDS AND CAN LIGHTS OK 2) BACK AREA KITCHEN LEFT TO INSPECT |
|
| 12/12/2011 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) CAN LIGHT TO HAVE SISMEC'S 2) LIVING CABLING TO BE SUPPORTED TO STRUCTURE. DO NOT USE SISMEC WIRES INTENDED TO SUPPORT T-BAR, WIRES TIE OFF BOTH ENDS 3) MC CABLE TO BE SUPPORTED PER CODE 12"-6' |