Permit: T11CM03236

Parcel: 12801013B


Addresses:

330 S WILMOT RD

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
01/26/2012 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
01/23/2012 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) LIGHT WHIPS OFF GRID
2) LOW VOLTAGE STRAPPED
3) PIPES EMT TO BE REMOVED OR PLUGGED
4) BOX TO BE ANCHORED
12/15/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :
1) FRONT AREA TEE BAR AND HARD LIDS AND CAN LIGHTS OK
2) BACK AREA KITCHEN LEFT TO INSPECT
12/12/2011 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) CAN LIGHT TO HAVE SISMEC'S
2) LIVING CABLING TO BE SUPPORTED TO STRUCTURE. DO NOT USE SISMEC WIRES INTENDED TO SUPPORT T-BAR, WIRES TIE OFF BOTH ENDS
3) MC CABLE TO BE SUPPORTED PER CODE 12"-6'