Permit: T11CM03236

Parcel: 12801013B


Addresses:

330 S WILMOT RD

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
11/30/2011 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
11/28/2011 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED NAIL PLATES FOR LABELS LESS THAN 1 1/4" FROM FACE OF STUD, 300.4 NEC
2) REPLACE BROKEN MC, ICE MAKER ROOM
3) CANNOT BEND LESS THAN 6 TIME RADIUS
11/23/2011 ELECTRIC - INTERMEDIATE Denied SUPPORT MC & FLEX PER CODE
MUST BE 1 1/4" FROM FACE OF STUD 300-4 NEC