Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/14/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/09/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) BOXES MORE THAN 1/4" OR 1/8" AROUND 314.20 AND 314.21 2) NEED PERMANENT REVISED PANEL DIRECTORIES 708.4 3) FRONT EXIT NOT WORKING-MISSING REAR SIGNS (4) 4) LABEL DISCONNECTS 5) SUPPORT M/C TO ERV |