Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T11CM03188
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/03/2011 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
10/27/2011 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : There is no access to the site.| 920* 1) LOCKED, NO ACCESS 1:05 PM |
|
10/25/2011 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED PLANS FOR LOADS FOR WATER HEATER-VERIFY IF PANEL LARGE ENOUGH FOR LOADS 2) MAINTAIN WORKING SPACE AT ELECTRICAL PANELS AND DISCONNECTS 110.26 3) PLANS DO NOT SHOW ADDED RECEPT 4) SUPPORT VDV CABLING 725.3 & 8, 800.3 & 24 AND 300.11 |
|
10/24/2011 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED |