Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T11CM03185
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/27/2011 | MECHANICAL - INTERMEDIATE | Approved | ||
10/17/2011 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) FLEX DUCT IS TO BE STRAPPED UP OFF OF DIRT UNDER TRAILER MINIMUM 4" ABOVE GRADE 2) UNIT DATA PLATE NOT PROPERLY INDENTIFIED 3) UNABLE TO READ AMP RATING ON FUSES, REPLACE FUSES THAT CANNOT BE READ 4) REMOVE PANELS AT REAR OF TRAILER TO BELOW FOR A COMPLETE INSPECTION |