Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/11/2012 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/10/2012 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 04/06/2012 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) PROTECT CONDUCTORS 352.46 AND 300.4 2) LABELING ON PV PANEL 690.17 3) SEPERATE GROUND AND NEUTRAL AT PV PANEL 4) NEED NEUTRAL TERMINATION AT SERVICE DISCONNECT 5) NEED REJECTION PINS |