Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/25/2011 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 10/12/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) CONDENSATE CANNOT TERMINATE AT A WASTE VENT, REROUTE TO A NON-HARD SURFACE AND TERMINATE WITHIN 6" OF GRADE 2) LINE SET INSULATION IS TO BE COATED FOR U.V. PROTECTION 3) POWER CORD TO INDOOR UNIT NOT PROPERLY INSTALLED 4) PROVIDE SECONDARY DRAIN AT INDOOR COIL |