Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T11CM03090
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/23/2012 | PLUMBING - INTERMEDIATE | Approved | ||
08/28/2012 | PLUMBING - INTERMEDIATE | Partial Approval | PLMG PRE SLAB AT MECH-ROOM OK | |
08/27/2012 | PLUMBING - INTERMEDIATE | Not ready for Inspection | DWV HEAD TEST FAILED | |
08/10/2012 | PLUMBING - INTERMEDIATE | Partial Approval | PHASE ONE COMPLETE. OK TO OCCUPY GANG BATHROOMS WILL REOPEN REQUIRED INSPECTIONS FOR PHASE TWO. |
|
06/13/2012 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
06/13/2012 | PLUMBING - INTERMEDIATE | Partial Approval | 1. Horizontal cleanout extensions at lavatories should be combos. Since the horizontal distance is minimum, no correction required at this time. OK to cover walls. | |
06/11/2012 | PLUMBING - INTERMEDIATE | Partial Approval | 1. All of the DWV system to be subjected to a test to ten feet. So that no joint or pipe shall have been tested with less than a ten foot head. 2. Cleanouts are to extend to the surface of the wall through a wye branch fitting. 3. OK to insulate hot and return piping. |