Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T11CM03062
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/05/2012 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
08/30/2012 | MECHANICAL - INTERMEDIATE | Partial Approval | SECURE B VENTS FROM LOWER UNITS BE SURE TO PROVIDE ACCESS TO APPLICANCES, PROVIDE MIN REQUIRE CLEARANCES FOR COMBUSTIBLES. CORRECT LINE SET INSULATION EXHAUST FAN TERMINATIONS. PROVIDE PROPER ROOD FLASHINGS FOR ALL PIPES ETC SECURE PEX(CORNER UNIT) PROVIDE ACCESS TO ALL UNITS ALSO PLANS AND PERMITS. |
|
08/01/2012 | MECHANICAL - INTERMEDIATE | Partial Approval | DOWN STAIRS | |
07/31/2012 | MECHANICAL - INTERMEDIATE | Partial Approval | DOWN STAIRS UNITS, WALLS OK. SUPPORT DUCTS, DRYER AND EXHAUST FAN WITH APPROVED METHODS. ISOLATE POX FROM METAL. INSTALL SAFETY STRIPS AT TOP PLATE. | |
07/27/2012 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |