Permit: T11CM03054

Parcel: 13626005B


Addresses:

3430 S MANN AV

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
10/28/2011 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
10/26/2011 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) TERMINATE CONDENSATE DRAIN WITH AN ELBOW AND A NIPPLE
2) HAVE ACCESS TO THE ROOF
3) BE SURE 3/8" COPPER FROM PUMP IS TERMINATED INTO PVC WITH A FITTING
10/24/2011 MECHANICAL - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
10/07/2011 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) PROVIDE A TRAP IN CONDENSATE DRAIN LINE
2) PROVIDE AN OVERFLOW SENSOR IN SECONDARY OUTLET
3) CONDENSATE CANNOT TERMINATE INTO A SEWER VENT
4) SUPPORT DRAIN LINE ON ROOF EVERY 6'
5) TERMINATE WITHIN 6" OF THE DIRT