Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/06/2012 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/21/2012 | ELECTRIC - FINAL | Denied | 1) #4 GEC MUST BE CONTINUOUS TO SES PER PLAN AND 690 NEC 2) NO SELF TAPPING FOR GROUND TERMINATIONS PER 250 NEC. 3) NO DBL LUGGING UNLESS LUSGS ARE RATED 4) COULD NOT LOCATE PANEL, NO ANSWER AT DOOR. 5) PROVIDE SPECIAL INSPECTIONS REPORT. 6) CONDUIT CONNECTIONS AT 8X8 JB. 7) ROMEX WIRING DUPLEX RECEPT NOT TO CODE. |