04/09/2013 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
04/04/2013 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
03/13/2013 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
SECURE AND SEAL DUCT TO DIFFUSER. SECURE DIFFUSER TO GRID. OK TO INSULATE DUCT. COMPLETE RETURN AIR. CORRECT SLOPE & SUPPORTS ON CONDESATE. SEAL JOINTS OF PIPE INSULATION. SHOW HOW UNITS 7&8 WILL SUPPLY SUFFICIENT MAKE UP AIR FOR HOOS EXHAUST
02/01/2013 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :* DELI AREA OK TO WRAP JOINTS RESTRROM/OFFICE/PHARMACY OK