Permit: T11CM03041

Parcel: 13506136E


Addresses:

2550 S KOLB RD

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
04/17/2013 PLUMBING - FINAL Approved IVRS - Inspection :*
04/15/2013 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
04/15/2013 PLUMBING - FINAL Not ready for Inspection BACK FLOW PROTECTION AT HYRID UNIT NOT EQUIRED PER ROBERT BOWLIN PO: HAS AIR CAP
INSTALL BACK FLOW SHOWN FOR ICE MAKER
SEPARATE CONDENSATE FROM BIN DRAINS. PROVIDE AN AIR GAP AT DRAIN TERMINATIONS. INSTALL A FUNNEL ATTACHMENT TO INDIRECT RECEPTOR. RO EQUIPMENT REQUIRES AN AIR GAP, ALSO PROPER USE OF FITTINGS. CPUC NOT COMPATIBLE W/ PVC. HOSE BIB AT HYBRID UNIT REQ VAC BREAKER AND FREEZE PROTECTION. TRAP SEAL PROTECTION FOR DRAINS W/OUT CONT USE EXTEND VTR AT ROOF HATCH. PROTECT ALL EXPOSED PLASTIC. COMPLETE OVERHEAD PIPE SUPPORTS. GAS REGULATOR VENTS SHALL TERMINATE MIN OF 3' FROM SPARK. SEALL ALL CLEAN OUT PLUGS - PLUGS SHALL BE TESTED TO RECOVER SCREW
04/09/2013 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
04/09/2013 PLUMBING - FINAL Partial Approval COMBI OVENTS ARE MISSING BACKFLOW PROTECTION. COMPLETE ALL WORK SHOWN ON PLANS, AND ANY OUTSTANDING ISSUES.
04/04/2013 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*SHOW HOW HYBRID HOUSE AND EVAP CONDENSER DONESTIC WATER SUPPLY IS PROTECTED FROM BACKFLOW AS REQUIRED PER CODE. CALL FOR AND HAVE APPROVED ALL OUTSTANDING REQUIRED INSPECTIONS.
03/26/2013 PLUMBING - FINAL Partial Approval IVRS - Inspection :*