Permit: T11CM03041

Parcel: 13506136E


Addresses:

2550 S KOLB RD


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T11CM03041

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
04/15/2013 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
04/04/2013 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
03/21/2013 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
03/05/2013 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*CORRECTION AT FREEZER PRE SLAB OK TO COVER
02/27/2013 PLUMBING - INTERMEDIATE Partial Approval piping insulation in walls ok bakery, product and meat freezer dwv and test ok. still need to see pre slab corrections noted on 1.24 for piping at freezer location
02/26/2013 PLUMBING - INTERMEDIATE Not ready for Inspection GAS TEST OK COPPER IN WALLS WITH TEST OK TO INSULATE PROVIDE A TEST ON CPVC AND DWV CORRECT VENTING AT 4" FD MAY NOT REVENT BELOW FLOOD LEVEL
02/21/2013 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*DELI AREA DWV W/ TEST THUR ROOF OK DOMESTIC WATER IN WALLS W/ INSULATION OK
02/20/2013 PLUMBING - INTERMEDIATE Partial Approval WATER OM WALLS

ALL JOINTS REQ A TEST. WHEN TESTING IN SECTIONS, THE UPPER PART OF THE PREVIOUSLY TESTED SECTION SHALL BE RETESTED SO NO JOINTS GO UNTESTED. O TO INSULATE WATER IN WALLS
02/05/2013 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*PHARMACY AND TOILET RMS; DWV W/ TEST OK. WATER OK TO INSULATE, PROVIDE TEST
02/04/2013 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*