Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T11CM03041
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/15/2013 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 03/18/2013 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. PARKING LOT TRENCH LITE POLE TO LITEPOLE AND HOME RUN 2. DELI PREP AREA CEILINGS OK 3. BAKERY HIGH VOLTAGE OK LOW VOLTAGE NOT READY |
|
| 03/07/2013 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. R7US NOT READY 2. UNDERGROUND FOR TRANSFORMER OK |
|
| 03/06/2013 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CONDENSOR B AND RACK A AND CONTROL CENTER FUSES AKE WRONG SIZE ON ROOF 2. COILS IN WALK IN OK 3. TERMINATIONS AND PENITRATIONS STILL TO BE INSPECTED 4. FROM TRANSFORMER POD TO BUILDING TRENCH WITH 5 PVC RUNS OK |